Language:
}
Normally Closed Manual Reset Solenoid Valve for Gas
M16/RM N.C.

P.max 0.5-6 bar
DN 15-20-25-32-40-50

Normally closed, manual reset solenoid valves for gas, suitable to shut off gas both to signal danger sent by gas detectors (methane, LPG, carbon monoxide and similar) or safety thermostats, and in the event of a power cut.

For additional safety, this solenoid valve can only be reset with the power supply on and only when the gas detector is not signalling danger.

IMPORTANT NOTE: The valve will not open by simply powering the coil. You must manually press the reset mechanism.

They can be equipped with CPI switches to control the valve’s obturator position (closed) remotely. Further information regarding the CPI switch is available in 7.0.

Reference standards: EN 161 - EN 13611.

In compliance with:

  • Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
  • PED Directive 2014/68/EU (versions with P.max = 6 bar)
  • EMC Directive 2014/30/EU
  • LVD Directive  2014/35/EU
  • RoHS II Directive 2011/65/EU
Documentation
Technical featuresIT-EN-FR-ESDownload
Type-approval certificatesRegulation (EU) 2016/426 (GAR) - EN 161Download
Type-approval certificatesPressure Equipment Directive (PED) 2014/68/EUDownload
Accessories / Spare partsVisual Closed Position Indicator VCPI..........IT-EN-FR-ESDownload
© 2024 Madas Srl